1.18.0
New Features
Dedicated Consumer Metering
The EMS now supports dedicated consumer energy meters for loads such as heat pumps, cooling systems, heating rods, non-integrated EV charging stations, etc. This makes it possible to monitor individual consumers directly in the platform. Installed consumer meters appear directly in the Dashboard's Consumption section. Additionally, a dedicated entry in the left navigation menu provides access to consumer overviews, detailed analytics, and comprehensive reports. To integrate a new consumer meter into EMS, navigate to Device Manager and add a new energy meter with the “Consumer” type assigned.
Consumers integration in Cloud UI
User-Managed Cloud-2-Cloud (C2C) API Access Control and API Keys
Management of Cloud-2-Cloud API read and write permissions has been introduced to the “System Settings -> External Interface -> REST API -> Cloud” section. The External Interfaces layout has been updated to support this workflow and enhance usability, by grouping the settings for Local REST API and Cloud-2-Cloud REST API under a single main section “REST API”.
User-generated, plant-specific API keys are now available to manage C2C REST API access. Administrators have the ability to rotate keys per plant, enhancing security and offering improved operational management for third-party integrations. Please note that the existing API keys issued before v1.18.0 will expire automatically on December 31, 2026. To prevent any unexpected operational downtime, all C2C API users are encouraged to generate a new key using this new functionality and update their systems accordingly before the end of the year.
Key Generation Process:
- Generating a Key: Users logged in as a Global Admin or Administrator can navigate to System Settings -> External Interfaces -> REST API -> Cloud, select the preferred validity timeframe, and create a new API key.
- Copying & Visibility: Upon creation, a copy-to-clipboard option is provided for convenience. For security reasons, the active key is only displayed once after its generation.
Revocation: Existing keys can be deleted to instantly deactivate them, after which a fresh key can be generated.
Notifications: Key expiration notifications will be triggered and sent via email to registered email addresses in the Plant State -> Email Alerts section.
External Interfaces - New C2C API settings
Enhanced Report Export
The default resolution for report exports has been updated from 1 minute to 15 minutes. This update covers all report categories (including Storage, Photovoltaic, Consumers, Charging Stations, and Overview) across every timeframe (daily, monthly, yearly, and total). Additionally, exported files now align CSV delimiters and decimal separators with the active UI language setting, and relevant column headers now feature units. The change is applied to .csv and .xlsx formats. Please note that the .xls format has been replaced with .xlsx.
External Control in Off-Grid Mode
The operation mode “External Control” now supports off-grid operation, allowing third-party microgrid controllers to control the plant during off-grid operation via the PSEC Modbus TCP Interface. The EMS provides the necessary status registers, operation mode control, and active/reactive power setpoint interfaces needed for advanced external supervision.
IT Network Integration for Auxiliary Devices
EV charging stations, energy meters for PV and consumers and PV data loggers can now be integrated via the external IT network (LAN 2) where rewiring to the internal OT network is not practical. This gives installers more installation flexibility. When creating a new device, the Link field now presents the two options, where LAN 1 (OT) refers to the internal network and LAN 2 (IT) to the external network.
Due to security reasons an energy meter of type “Grid” cannot be added via the IT network.
Device creation - "Link" field options
BMS Balancing Notifications & External APIs
The EMS now exposes battery balancing information more clearly by notifying users when balancing is requested by the BMS and by making that state available through the external interfaces. This helps operators and upstream systems to monitor balancing requests and their potential impact on plant operation. Please consult the REST API or Modbus TCP interface documentation for more information.
Ziehl EFR4002IP new device integration
Added integration support for the Ziehl EFR4002IP as a grid-only meter.
Changes
- Plant Permission Group Reassignment: Plants can now be reassigned to a different permission group instead of being deleted and recreated. This makes handover from partner-managed commissioning groups to end-customer groups much simpler and helps preserve existing plant settings.
- Improved User Search Across Permission Groups: User search has been improved so users can be found more easily even when they were not created at the root level or when the exact permission group is not known in advance. This reduces friction for service and administration workflows.
- Devices Section Renaming: The former “Devices” section has been renamed to “Device Manager” in English and “Gerätemanager” in German.
- Device Manager:
- The ABL eM4 EV charger selection has been simplified by consolidating the model list into a single entry (“ABL eM4 22 kW”).
- The former Pylontech Humidity and Temperature “LEMS” sensor has been renamed to “HVAC Sensor” for clearer identification.
- Updated Hardy Barth EV charging station model names in device selection to display “[Salia]” and “[eCB1]” instead of “V1” and “V2”.
- Grid Operator Control Box Contact Configuration: The contact type for the grid operator control box is now configurable. Users can select Normally Open (NO) or Normally Closed (NC) behavior to match the hardware configuration.
- DSE Generator Alarm Text & Failure Reporting:
- Generator notifications now show the actual DSE alarm text instead of only a generic error message. The EMS also reports DSE control unit failure explicitly, making generator issues easier to understand and troubleshoot.
- Have also added support for reading and displaying custom controller-configured unnamed alarms and alarm texts for DSE 8xxx / G86xx gensets.
- §14a EnWG Power Limitation State Retention: If a GPIO read fails, the EMS retains the last valid dimming state instead of resetting the limitation.
- System Settings Navigation Clarity: System Settings navigation has been reworked in Multi-BESS contexts so it is clearer whether the user is working in global settings or edge controller settings. This reduces ambiguity when moving through nested settings areas.
- Multi-PV Plant Forecasting: Forecast accuracy is enhanced for complex solar setups by considering multiple PV plants per system rather than limiting evaluations to a single plant.
- Permanent IP Address Default: IP address expiration controls have been removed from the LAN settings UI, and non-expiring IP behavior is now the default. This simplifies configuration and removes settings that no longer add useful value in normal workflows.
- Multi-BESS Accordion Display: Accordion behavior in Multi-BESS views has been improved for a more consistent and understandable display compared with standalone setups. This makes navigation easier in larger systems.
- BESS creation: Added new Pramac BESS models (BSO XT series and BSO HYB 60/126) to the BESS model selection.
- Photovoltaic section: Resolved naming inconsistencies between Photovoltaic Overview and Details views to uniformly display "Energy" labels and “PV Production”.
- Mobile App: link to Help Pages has been removed.
Bug Fixes
- Fixed an issue where users with the role “User” could get an “Access denied” message in User Management and see an empty user list instead of read-only visibility for their permission group.
- Fixed an issue where chart legend entries in reports were truncated instead of wrapping.
- Fixed an issue where consumer and EV charging entries in Energy Monitor tooltips behaved inconsistently compared with PV and storage entries.
- Fixed an issue where LAN 1 (OT) settings stayed in an unsaved state after a successful save and continued to warn users when leaving the page.
- Fixed an issue where spot-market prices could stop appearing in reports when ENTSO-E data arrived without a sequence number.
- Fixed an issue where changing tasks without a grid meter could lead to a broken state and operational instability.
- Fixed an issue where charging and discharging operation modes did not work correctly when a system had no grid meter configured.
- Fixed an issue where the Add Plant button could remain disabled or not respond as expected.
- Fixed an issue where Inpower inverter notifications were missing translation keys.
- Fixed an issue where the maintenance page appeared inconsistently, allowing parts of the UI to remain accessible during maintenance mode.
- Fixed an issue where the Data Privacy Policy link on the disabled location map did not work.
- Fixed an issue where the old permission group dialog was still used in one part of the mobile app.
- Fixed an issue where deleting devices that were part of an IBU or FSS showed a technical error message instead of a clear user-facing explanation.
- Fixed an issue where old edge location data was shown next to the plant name instead of the plant location.
- Fixed an issue where the AC power gauge direction in BESS details was visually inverted compared with Storage Overview and Backup Overview.
- Fixed an issue where reserved SoC violations did not show the intended specific user notification message.
- Fixed an issue where manual battery operation messaging incorrectly suggested that all current charging plans would stop.
- Fixed an issue where user management could render an empty list when a user without standard profile fields was present in a permission group.
- Fixed an issue where remote PV energy values were not included in reports for day, month, and year periods.
- Fixed an issue where a control point with a negative value was not displayed correctly in the dashboard context where applicable.
- Resolved an issue causing slow transitions in Multi-Use mode when switching from self-consumption optimization to peak-shaving.
- Fixed IP validation to detect active DHCP leases during device setup. Duplicate IPs, Ports, and Unit-IDs are allowed only for different device types.
- Fixed an issue where sometimes the serial number was displayed as empty for Inpower 125K inverters.
1.17.9
Bug Fixes
- Schneider Energy Meter - Resolved issue with the meter integration.
1.17.6
Changes
- EVCS - ABL eM4: We now also support the Controller-Extender group functionality.
- Added off-grid support to the Inpower 125K inverter driver for parallel operation with generators and reactive power control support.
1.17.5
Changes
- This update includes important security fixes and improvements.
Bug Fixes
- Improved behavior of the peak shaving task when grid meter communication fails.
1.17.4
Changes
- Adjusting EVCS load management for ABL Charging Stations.
- Adding 2 decimal places to the power value of the ABL EVCS.
1.17.3
Changes
- Adjusting the new trickle charge strategy with the same threshold for all used battery types.
1.17.2
Changes
- Adjusting the trickle charge strategy to minimize high frequent recharging.
Bug Fixes
- PSEC 1.17 update - An improvement for the long-lasting and non-running edge updates.
1.17.1
Bug Fixes
- Capacity BSO MAX 125/261 — Resolved an issue for showing 0kWh capacity.
- Local UI Multi-BESS Secondary — Improved maintenance operations.
1.17.0
New Features
Parallel Generator (Genset) Control
Added support for managing and running multiple generators (Gensets) simultaneously in parallel. Multiple devices may be configured in the Device Manager and:
- The dashboard bubble displays all configured units.
- The Genset detailed view incorporates comprehensive information for all units.
- System overviews and generated reports aggregate data across all connected units, offering filtering capabilities by genset within reports (analogous to PV filtering).
Generac Power Zone Controller Integration
Integrated Generac Power Zone PRO Sync controllers to integrate gas generators in off-grid setups.
Hardy Barth EV Chargers integration
Expanded system compatibility to support Hardy Barth electric vehicle chargers (V1 & V2), enabling both monitoring and full load management functionality. The following EVCS models can be added and used in the EMS:
NB: These devices use the REST API protocol. Select “REST API” when adding them in Device Manager.
UPDC Integration
Added support for UPDC load-shedding units with PBI inverters to fulfill grid stability requirements in the Italian transmission system (Terna). The remote-controlled device installed at substations or large customers automatically disconnects predefined electrical loads when Terna detects critical grid conditions (like frequency drops or system emergencies), helping stabilize the power system and prevent blackouts.
Centralized Reactive Power Control via PSEC
Smart Power Plant Controllers / EZA-Regler can now send plant-wide reactive power targets directly to the PSEC instead of having to communicate with each battery inverter individually. The PSEC automatically distributes the target across all connected battery inverters to regulate grid voltage and optimize plant performance. Refer to the PSEC Modbus TCP interface documentation for further details.
Centralized Battery Inverter Power Curtailment via PSEC
Smart Power Plant Controllers / EZA-Regler can now send active power curtailment commands directly to the PSEC via its Modbus TCP interface. The PSEC automatically applies and balances the power limits across all connected battery inverters, removing the need to manage and curtail each inverter individually. Refer to the PSEC Modbus TCP interface documentation for further details.
Battery Flexibility Metrics via Standard Modbus Interface
Third-party energy management systems, SCADA systems, and Smart Power Plant Controllers / EZA-Regler can now read available battery charge and discharge capacities directly through the standard Pramac Modbus TCP interface. This enables integration partners to monitor real-time battery energy availability for grid import and export without requiring specialized market interfaces. Refer to the PSEC Modbus TCP interface documentation for further details.
Configurable Sensor Relay Types
Added configurable relay contacts (Normally Open / Normally Closed) for temperature, smoke, and ignition sensors. They can be set for each device in the device specific settings. Example:
Changes
- Operation Mode Naming & Sorting — Harmonized and organized operation mode names in English and German for clearer, more intuitive navigation.
- Clearer Forecast vs. Actual Charts — Updated PV production and consumption charts to make actual measurements and forecasts visually distinct in graphs and legends.
- Multi-BESS Version Overview — Updated the software version dialog to clearly show individual controller versions in Multi-BESS systems.
- Devices Section Polish — Refined the layout and user experience in the Multi-BESS Devices section.
- Hardware Connection Pin Selection — Updated device settings configuration to only show valid pin numbers matching the selected hardware module.
- Datalogger Deletion Protection — Added safeguards to prevent removing a datalogger while PV optimization is active during SSC operation.
- Collapsible Fire Suppression System View — Made the Fire Suppression System (FSS) section collapsible for a cleaner interface.
Bug Fixes
- Consumption Reports — Resolved an issue where daily energy values in reports showed conflicting numbers for the same day.
- Inverter & Battery Error Details — Fixed an issue where displayed error details did not match active device statuses.
- Grid Dimming Allocation — Fixed grid dimming handling so battery charging power limits are correctly calculated without being cut to zero by consumption.
- Serial Communication Settings — Fixed an issue where saving communication settings for serial link modules would fail.
- Operation Without Grid Meter — Corrected battery inverter charging behavior in Peak Shaving and Multi-Use modes when a grid meter is not present.
- Task View Display — Cleaned up the Peak-Shaving operations task view to remove unnecessary internal parameters.
- Plant Edit Form — Fixed the plant editing dialog so the save button remains disabled until changes are made.
- Market Price Data Processing — Fixed electricity price processing so missing data in one bidding zone does not interrupt price updates or cause unintended battery charging.
- EV Charger Current Distribution for ABL eM4 charger — Fixed charging current allocation so power is properly directed to actively connected vehicles rather than split across empty ports.
- Plant Management Dialogs — Fixed an issue where plant creation, edit, and delete windows did not automatically close and update after saving.
- Charging Stations Models — Added missing Alpitronic HYC 200 fast charger configurations to the device selection list.
- Connection Notifications — Improved controller connection alerts to prevent notifications during brief network dropouts.
- Date & Calendar Formatting — Standardized date formats consistently across all cloud views.
1.16.6
Bug Fixes
The following issues were addressed:
- Solved problem regarding the accessibility of the local UI
1.16.5
Bug Fixes
The following issues were addressed:
- Resolved plant status escalation, when one part of a Multi-BESS system is offline.
- Improved handling regarding the SPPC limitation of EVCS.
1.16.4
Bug Fixes
The following issues were addressed:
- Smart Self-Consumption: Fixed an issue where charge period optimization incorrectly delayed charging before cost peaks resulting in BESS charging during higher cost period and discharging during lower cost period.
- Remote Meters: Resolved an issue where remote meters were not correctly filtered by permission group during the addition process.
Please note that these updates only required a targeted deployment of Cloud services, so the Cloud version listed in the Version Notes remains unchanged.
1.16.3
New Features
New device integration: Schneider ION9000 series energy meter
The whitelist of supported energy meters has been expanded to include the Schneider ION9000 series energy meter for grid and PV monitoring purposes. The device can be configured within the Device Manager as either a PV or a grid meter.
Bug Fixes
- Fixed an issue where manual operations, balancing, and trickle charging were incorrectly limited in plants without a grid meter. The EMS now ensures that when no grid meter is installed, manual operations, balancing, and trickle charging are flat-clamped to the configured mains connection power limit within the Grid Connection Point settings.
1.16.0
Highlights
- Multi-BESS Architecture: Scalable plant-level management with a unified view for multiple Battery Energy Storage Systems.
- New Off-Grid Operation Modes: Added "Battery-only Mode" and "Full Mode” as new off-grid operation modes.
- Smart Self-Consumption (SSC): New option to prevent PV grid feed-in during negative electricity prices by curtailing the surplus produced power.
- Cloud-2-Cloud API: Integrated SoC as new datapoint into the energy values endpoints.
- Energy Meter Flow-Inversion: Added software-based flow inversion for energy meters.
- Key Fixes: Optimized SSC algorithm for multi-peak utilization and corrected BMS DC current visibility.
New Features
Multi-BESS Architecture
Operating Multi-BESS installations is now more scalable and user-friendly. With the introduction of the plant as the primary operational object, users benefit from an intuitive experience that provides a unified view and simplified oversight of the entire system from a single location.
What is new
- Plants are now the main way to view systems
A new logical Plant level has been introduced to the platform, positioning it above individual edge controllers. A plant can represent either a standalone installation or a Multi-BESS setup configuration, featuring a single primary controller along with one or more secondary controllers.
- Plants are now the main top-level object for monitoring and navigation.
- Edge Controllers remain visible as a separate section for controller-level management.
- Each plant groups the controllers (and BESS) that belong to the same customer system.
- A plant gives users one place to understand the overall state of their energy storage installation.
- Operationally, each plant has a primary controller and one or more secondary controllers. Upon a new installation, the primary controller must connect to devices like energy meters, data loggers, charging stations, gensets, and GSB. All BESS-specific devices (inverters, BMS, peripherals) must connect to their corresponding controllers.
2. New Plants section in the Portal
A new Plants section has been added to the Portal. This is the main entry point for viewing and managing customer systems.
In this new section, users can:
- View available plants, including on a map if an address is provided.
- Search plants by name, PSEC serial number, or permission group.
- Open a plant directly from the portal.
- Expand a plant to see its assigned controllers.
- Global Admins or Administrators can create, edit, delete, and manage plants and their controllers. Plants can only be created using controllers from the chosen permission group.
Plants page
3. Edge Controllers section replaces the old edge-centric portal model
The previous edge-focused navigation has been simplified. The Edge Controllers section now supports controller-level tasks while the overall operational view moves to the plant level.
- Controller search remains available (by name, serial number or permission group (new));
- Status filtering remains available;
- Users can still inspect controller details;
- Map view no longer available;
- Global Admin or Administrator user roles can assign controllers to available permission groups.
Note: End users should expect more day-to-day work to happen from the plant view, while the Edge Controllers area supports more technical or administrative tasks during new system commissionings.
Edge Controllers page
4. Plant UI replaced Edge (PSEC) UI
Open the “Plant UI” via the location pin next to the plant name to view system details.
Existing systems in the Production environment will automatically get a corresponding plant upon release. In the plant UI, users can still:
- View the dashboard (energy monitor and data widgets):
- When hovering over the Storage bubble, the enhanced Storage tooltip now displays the complete list of BESS units within a multi-BESS setup, allowing users to view the individual IBUs for each BESS if there more than one IBU is present. Additionally, the displayed State of Charge (SoC) now reflects usable instead of nominal SoC.
Dashboard Storage bubble
- Manage operations.
- Manage Backup and Off-Grid settings, if available.
- Visualize reports.
- Manage and view storage data (in multi-BESS installations, users can perform individual maintenance for each BESS).
- Visualize Photovoltaic, Charging Stations, and Genset data, if available.
- Manage System Settings, which are now split into:
- Global Settings: Plant-level configurations, including Location Settings, Grid Connection Point, Plant State and External Interfaces.
- Plant State: consolidates all notifications from every controller across the plant. The same applies to the Notifications Center. To distinguish the notifications from different controllers, they are prefixed with the controller's serial number.
- External Interfaces: This section moved to the plant level as only the primary controller handles the interaction. Cloud-2-Cloud REST API and Modbus Interface users can continue as before, targeting the primary controller. New endpoints for Cloud-2-Cloud and Local REST APIs also allow calls using plant_id, which matches the primary controller's edge_id.
- Edge Controller Settings: Individual controller (PSEC) settings.
- Global Settings: Plant-level configurations, including Location Settings, Grid Connection Point, Plant State and External Interfaces.
System Settings page
5. Local UI - Differentiation between Primary and Secondary Controllers
While the Local UI for a primary controller mirrors the cloud-based Plant UI, the Local UI for a secondary controller is restricted exclusively to the Storage and System Settings (Edge Controller Settings) sections.
Primary PSEC Local UI menu
Secondary PSEC Local UI menu
Who is affected
- End Users:
- The plant view is now available for all users, not only for those who own a multi-BESS system; all existing users can now find their systems in the portal under the Plants section. Post-release, users must visit the Plants section to locate their system in the Portal.
- The new Multi-BESS Architecture feature is especially relevant for users owning or managing systems with multiple BESS units connected to a single grid connection point, requiring plant-level oversight.
- Installers and Technicians: those who commission new systems post-release need to use the new workflow:
- Find the controllers in the new Edge Controllers section;
- Note: each new edge (PSEC) automatically gets a plant created in the Cloud. If the controller is not found in the Edge Controllers section, search it in the Plants section and delete the plant. This will cause the controller to appear in the Edge Controllers section and allow the option to be (re)assigned to a permission group.
- Assign them to the desired permission group;
- Create a new plant with the desired controller(s) at the desired permission group;
- Connect devices such as energy meters, charging stations, gensets etc. to the primary controller only, in case of a multi-BESS setup;
- In case a BESS is not preexisting before the commissioning, the Cloud UI or Local UI can be used to create the devices such as inverters, BMS and peripherals and afterwards the BESS (and its IBUs).
- Find the controllers in the new Edge Controllers section;
- API/Integration Developers: Affected by the introduction of new endpoints for Cloud-2-Cloud and Local REST APIs that now support plant_id. However, the usage of the new endpoints are optional at the moment as the old endpoints using edge_id continue to be supported.
Constraints and Compatibility Notes
- Multi-BESS systems require all controllers to run version 1.16.0 to function correctly.
- For controllers on versions below 1.16.0, Cloud 1.16.0 introduces the following limitations:
- Plant settings do not reach older edges: Changes to location, grid, date-time, and plant name are saved to the cloud (showing a success message) but are not transmitted to older edges.
- Date-time settings can revert: Time zone or automatic-time portal updates can be overwritten and reverted by older edges periodically uploading their own location data. Location address and grid settings do not revert.
- Do not group older edges: Older edges grouped into a plant will not receive their primary/secondary roles and will continue to operate independently. Only group edges after all run version 1.16.0.
- Read-only views remain functional: Storage overviews, BESS data, notifications, and reports work normally with no data loss expected.
- No portal warnings: The portal displays the software version but lacks update hints or feature restrictions, making all features falsely appear available for older edges.
New Off-Grid Operation Modes
- Battery-only Mode: This lets the system run entirely on battery power without needing to start the generator, providing more operational flexibility.
- Full Mode: Optimizes off-grid performance by enabling the generator and battery to work in tandem, ensuring stable power delivery for BESS operations.
Smart Self-Consumption - Additional PV optimization
The PV optimization of the Smart Self-Consumption operation mode now includes an additional setting that allows users to enable zero feed-in during negative electricity prices. When activated, PV grid feed-in is prevented during negative price periods, helping to avoid financial losses caused by negative feed-in prices or penalty charges.
- PV optimization proactively creates battery capacity before negative price periods.
- If this alone cannot prevent grid feed-in, the optional zero feed-in setting curtails PV generation to eliminate grid export.
- The feature can be enabled via the dedicated toggle in the Smart Self-Consumption task in Operations Management.
- The activation of this feature requires the presence of a supported PV data logger, added within the device manager.
Smart Self-Consumption task template
Modbus TCP interface adds usable SoC register
The PSEC Modbus TCP interface now includes a new register for usable SoC (Address 1080), enabling users to retrieve the same usable SoC value displayed on the UI dashboard. To improve clarity, existing registers were also renamed: register 1004 is now soc_nominal and register 1078 is soc_nominal_remaining_wh
Cloud-2-Cloud API energy endpoints extended with optional SoC parameter
Users can now gain deeper insights into system health by accessing battery SoC data alongside historical energy values through the new optional include_soc parameter. Consult the API documentation for more information.
Invertible energy meters
Saves time and reduces maintenance costs by allowing users to software-invert current flow direction directly from settings, eliminating the need for physical on-site re-installation.
Energy meter device-specific settings
Changes
The following changes are introduced:
- Dashboard energy widgets: Ensures users always have the most accurate, real-time information with new background updates for header KPI widgets.
Bug fixes
The following issues have been resolved:
- Fixed an issue in the Smart Self-Consumption (SSC) algorithm to allow battery discharging/recharging during low-cost periods before a second cost peak, improving multi-peak utilization. Also corrected logic to prioritize charging during negative energy prices.
- Fixed missing (showing 0) BMS DC current values in the BESS details view for ZYC systems.
1.15.6
Bug fixes
- The issue regarding the Pylontech M7 BMS improper driver mapping is now fixed.
1.15.5
Bug fixes
- Resolved issue with the forecast for Smart Self-Consumption
1.15.4
Bug fixes
- Fix regarding PV limitation functionality of SunGrow datalogger
1.15.3
Changes
- Integration of the Huawei Smart Logger as PV data logger
Bug fixes
- Correction of the displayed Backup Mode.
- Resolved issues with the remote meter integration.
- Resolved: IBU gets blocked in CHECKING state
1.15.1
Changes
- Improved calculations for the new Self-Consumption widget and Self-sufficiency widget.
Bug fixes
- Correction of the wrong BESS capacity.
- Adding the Fire Suppression System to the BESS status escalation.
- Improved Weiguang fan device control to reduce spam notifications and enhance user experience - for all systems.
1.15.0
New Features
Integration of the new BSO MAX 125/261 product
Added support for the new BSO MAX 125/261 system, including the Inpower INPPCS-125K inverter and Pylontech M7 BMS. The integration enables configuration, monitoring, and fault management of the system within the EMS, providing the same functionality as existing supported inverter and BMS devices.
Enhanced Smart Self Consumption to avoid PV feed-in during negative price windows
The Smart Self Consumption operation mode is now able to prevent the feeding of solar energy into the grid when spot market prices turn negative. Instead of exporting surplus PV at unfavorable rates, the system intelligently reserves battery capacity to absorb that energy for later self-consumption.
Two new settings give users now full control over the SSC functionalities:
- PV Optimization – automatically avoids feed-in during negative price periods
- Grid Optimization – enables price-optimized grid charging
Both are enabled by default and can be adjusted to match users’ preferences.
Fire Suppression System (FSS v2)
Added an enhanced Fire Suppression System integration for BESS units. The system continuously monitors gas, temperature, and smoke sensors to detect early signs of malfunction and prevent thermal runaway. Based on sensor readings, it automatically triggers escalating safety actions — including HVAC force cooling, BESS Safety Stop, and HVAC shutdown. Users can create, edit, and delete an FSS configuration per BESS via the three-dots menu in the Storage Details page, assigning available sensor devices (gas, temperature, smoke) and aerosol suppression systems. FSS status is displayed in a consolidated tile under BESS Peripherals with color-coded sensor states. Supports multiple sensor vendors and models (Kentec, Pramac). The pre-existing "Fire Suppression System" device type in Device Manager has been renamed to "Fire Control Panel" for clarity.
To illustrate the FSS user interface during normal state, please refer to the images below.
Alarm state:
New endpoints in the Cloud-to-Cloud REST API
C2C REST API: Energy values endpoint
Added a new Cloud-to-Cloud REST API endpoint (/api/v1/edge/{edge_id}/energy_values) that allows external partners to retrieve historical and near-real-time energy data for a given system. The endpoint returns values for PV production, load consumption, grid consumption, grid feed-in, BESS charging, and BESS discharging at configurable resolutions (5 min, 15 min, 1 hour, or 1 day), with optional totals. The request is authenticated via API key and includes input validation and a 30-day maximum time horizon.
C2C REST API: Schedule endpoint for setpoint plans
Added a new Cloud-to-Cloud REST API endpoint (/api/v1/edge/{edgeId}/schedule) that accepts a 24-hour plan of control setpoints in 15-minute intervals (96 entries). This schedule serves as an automatic fallback — if no real-time command is received via the existing /control endpoint within the 5-minute timeout, the system uses the provided schedule to charge (positive values) or discharge (negative values) the BESS. This ensures operational continuity and resilience against connectivity issues. The endpoint includes input validation, handles overlapping setpoints by using the latest, and requires API key authentication.
Please consult the API documentation for more information.
§14a EnWG grid operator dimming support
Added compliance with §14a EnWG by supporting grid operator curtailment ("dimming") signals. A new device type — Grid operator control box — can be added in the EMS, which receives the DSO signal via a potential-free dry contact (GPIO). When the dimming signal is active, BESS grid charging power is automatically limited to 4.2 kW. Normal operation resumes once the signal is withdrawn; grid feed-in remains unaffected.
Added support for Wallbox SUPERNOVA 240 charger
The Wallbox SUPERNOVA 240 (240 kW / 2× CCS2) has been added to the list of supported Wallbox chargers in the device manager. Users can now select and configure this charger directly through the EMS interface.
Added support for Mennekes AMTRON 4Business 700 charger series
The device manager now includes the "AMTRON 4Business 700" series (11 kW and 22 kW, Typ 2) as selectable chargers, ensuring all officially supported Mennekes EV charging stations are available for configuration in the EMS.
Changes
1. Dashboard, Sidebar Menu and new widgets:
- The dashboard has been redesigned with a cleaner, more responsive layout. Unused sections and excessive scrolling space have been removed, and large device lists (IBUs, EVCSs) are independently scrollable. Please refer to the below image to see the simplified Energy Monitor and sidebar menu for a system that does not have any EVCS devices nor PV production:
- Three new daily insight widgets have been added:
- Charged / Discharged Energy – displays the total energy charged and discharged by the storage system today (kWh).
- Self-Consumption – shows how much of today's local production was consumed on-site rather than fed into the grid (% and kWh).
- Self-Sufficiency – shows how much of today's consumption was covered by locally produced energy (% and kWh).
- The Weather and CO₂ Savings widgets have been removed. Dashboard sections and energy monitor bubbles (PV, EVCS, Genset) are now conditionally displayed — they only appear when the corresponding devices are installed in the system, keeping the interface clean and relevant to each site's configuration.
2. Handling energy value drops on Janitza energy meters: Resolved an issue where Janitza meters occasionally reported decreasing energy values (production/consumption), causing incorrect spikes in reports. The system now detects and ignores short-duration glitches in energy readings, ensuring consumption and production reports remain accurate and free of anomalous spikes.
3. Enhanced charging control to maintain reserved SoC: Added intelligent charging power control to ensure the battery's reserved State of Charge (SoC) is maintained. When the actual SoC drops below the reserved level, the system now automatically initiates charging at the appropriate power level — while respecting grid connection point limits and control point constraints. This ensures the reserved energy buffer is always available for backup scenarios without violating physical grid limitations.
4. PV plant configuration improvements & PV forecast clipping: Redesigned the PV plant configuration interface with improved usability, including intuitive azimuth and tilt angle controls with slider and direct input. Introduced PV forecast clipping, which caps the PV forecast value at the inverter's Max AC Power — ensuring forecasts never exceed what the inverter can actually deliver. Also added sun tracker support (fixed orientation / tracking mode) for more accurate forecast parameters. Please refer to the image below:
5. MAC address field removed: Adding a new network device does no longer require the input of its MAC address. The existing MAC address field has been removed.
6. Output PIN configuration for GPIO fan device: Users can now select and configure the output PIN for GPIO fan devices directly from the device specific-settings.
7. Full battery discharge prevention in off-grid systems without a Genset: the EMS now automatically shuts down inverters when battery SoC drops below the minimum safe threshold to prevent full discharge and BMS errors.
Bug Fixes
The following issues have been resolved:
- The External API no longer silently serves outdated data when the MQTT broker connection is lost. It now returns a 503 error, so API consumers can detect and handle the issue.
- Eliminated false fan outdoor temperature warnings generated at system startup when fans are correctly configured.
- Indoor temperature now displays correctly in the Fan UI when fans are controlled by humidity and temperature sensors.
- SSC load forecast no longer produces negative values — negative load values are now clamped to zero before being passed to the forecast trainer, preventing incorrect training data.
- Error notifications being attributed to the wrong devices, causing confusion for customers have been fixed. Fault announcements now correctly identify the actual device reporting the error.
- Spot market prices report no longer shows gaps or incorrect values when price data is incomplete.
- Fixed a technical issue that occasionally caused interruptions in load predictions.
- The external control interface (Modbus TCP) was reporting double the actual PV power values due to the datalogger value being summed twice. PV data passed via external control now matches the values shown in the UI.
- When the grid meter became unresponsive, the system continued operating without detecting the issue. The grid meter stall is now properly detected and triggers an error state, stopping the system as expected to prevent unsafe operation.
1.14.9
Changes
- Improved reports energy values caused by SMA data loggers wrongfully reporting data drops
1.14.8
Changes
- Resolved manual file update issues via Local UI.
- Fixed occasional missing load forecasts.
1.14.7
Changes
- Improved reports energy values caused by SunGrow and SMA data loggers wrongfully reporting "zero" values.
1.14.6
Changes
- Improved Weiguang fan device control to reduce spam notifications and enhance user experience.
1.14.5
Changes
- Improved reports energy values caused by previous energy value read from the devices being “zero”.
1.14.4
Changes
- Enhanced reporting for energy values provided by SolarLog data loggers, addressing issues where device-provided energy data would decrease inaccurately.
1.14.3
Changes
- Improved PV curtailment strategy during Off-Grid mode to avoid inverter overcurrent faults.
- Improved reports energy values caused by SolarLog data loggers wrongfully reporting "zero" values.
1.14.1
Changes
- An update to the available BESS models has been implemented, which now incorporates a Generic PRO model.
Bug fixes
- Resolved the problem regarding the reading of unsupported registers in legacy inverter versions.
- Customer portal - Locations: Fixed an issue where selecting "All" in pagination settings caused the system list to appear empty and reset to a default page size.
1.14.0
New Features
Implementation of a dynamic control point for peak shaving operation
The peak shaving operation mode has been enhanced to support dynamic configuration of the control point via the Modbus TCP interface. For detailed technical specifications on integrating this functionality, please refer to the Pramac EMS Modbus TCP interface documentation.
Advanced Microgrid Control
Pramac C&I PRO BESS systems now include advanced microgrid control. This enables users to monitor and configure Backup and full off-grid operation, including genset integration and PV curtailment management. New user interface components have been added to support monitoring and configuration of these modes.
Highlights
- New “Genset” section in the UI
- Dedicated area for monitoring with aggregated power and energy values
- Genset production data integrated into the “Overview” report
- New section “Backup” or “Off‑Grid” depending on the system’s use case
- Overview
- Immediate status overview of current operation: On‑Grid, Backup – Running/Stopped, Off‑Grid – Running/Stopped
- Key live metrics at a glance: SoC (net), BESS charge/discharge power, consumption, PV power, Genset power
- Pramac Smart Transfer Switch (PSTS) status with detailed voltage and breaker information
- Off‑Grid operation controls
- Blackstart button to start fully islanded operation without grid connection (with safeguard checks)
- Stop operation button to safely stop backup or off‑grid modes and return the system to standby
- Backup configuration & SoC reserve
- Configurable Reserve SoC to protect a minimum battery level for backup operation
- Clear Backup status (Available / Limited / Not available) based on PSTS, genset and SoC condition
- Off-Grid controls for setting Target Voltage and Target Frequency
- Genset integration
- Genset startup clearance toggle (for maintenance / safety use cases)
- Configurable SoC thresholds for Genset start/stop and Max Charge Power and Max Discharge Power for the BESS from the Genset.
- PV power limitation during off‑grid/backup
- Automatic limitation of PV production surplus implemented via supported PV dataloggers (SMA Data Manager, Solar‑Log, Sungrow)
Changes
- Modbus TCP Interface extension: External devices can now access additional data points via the Modbus TCP interface, including BESS state of charge (Wh), maximum charge and discharge power, grid import and export energy, as well as BESS and PV energy flows. For further details, refer to the Modbus TCP interface documentation.
- Operational IBU data display: Calculations for BESS capacity and nominal SoC now consider only operational IBUs.
- Pagination in Portal: Users can now view all systems within the Portal.
- Local UI Update: The Reports section has been removed from the Local UI to streamline the interface and focus on core functionality.
- Cloud Application Performance Improvements: Performance of cloud microservices has been improved
Bug Fixes
The following issues have been resolved:
- Restored the missing scale in the Dashboard Forecast widget in the mobile app (portrait and landscape) on Android and iOS.
- Fixed an issue where the inverter error INVERTER_ERROR_USER_DC_LIMIT_MAX was not displayed as a UI notification.
- Fixed incorrect “Unknown inverter error” notifications caused by lost Modbus communication with the inverter.
- Fixed an issue where the Energy Sources widget displayed an extra day beyond the 7-day range.
- Fixed an issue where disabling GateKeeper did not fully block external inverter connectivity.
- Fixed display issues in the mobile dashboard for systems with many IBUs, charging poles, or PV meters.
- Fixed an issue where PV plants/meters in the PV Details section were not sorted alphabetically.
1.13.0
New Features
Smart Self-Consumption
A new operation mode (“Smart Self-Consumption”) has been added to the EMS. This feature is designed to minimize electricity costs by optimizing the charging of the BESS. It uses load forecasts, PV forecasts and day ahead spot-market prices to determine the most cost-effective intervals when to charge the BESS.
Forecasts
- Load forecast: Using an in-house machine learning model, the load forecast service provides a prediction of the system load for the upcoming 48 hours based on the previous 3 months of historical data. This service runs and provides predictions every 15 minutes.
- PV production forecast: By integrating with Meteoblue, the system forecasts PV production for the next 48 hours. These predictions are based on specific plant parameters, which must be configured in advance as detailed below.
- Day-ahead spot-market prices: Through its integration with entso-e, the EMS retrieves day-ahead spot market prices based on the system's designated Bidding Zone.
The forecasted values are visualized in the following sections:
- Reports -> Overview,
- Forecast widget in Dashboard,
- Photovoltaic Report,
- Spot-market prices report.
New operation mode
A new operation mode (“Smart Self-Consumption”) is now available in the Operations Management.
Important Note: in order to use this feature please contact us.
Genset displayed in Energy Monitor
The EMS now displays the Genset in the Dashboard, when such a device has been added in the EMS.
Balancing power input field
Users can now specify the balancing power. It defaults to the inverter's nominal power. The actual balancing power is limited by both the BMS and inverter, applying to manual and scheduled balancing.
Changes
- Improved edge application performance and maintainability.
- Added BESS models: "BSO MAX 90/188" and "BSO MAX PRO 90/188."
- The active IBU count under Storage > Details now includes IBUs with a “warning” status.
- Adjustments have been made to mitigate excessive notifications caused by volatile communication issues between the PSEC and devices.
Bug fixes
The following issues have been addressed and resolved in this release:
- The correct unit of measure (RPM) for fan speed is now visible in Storage -> Details -> Peripherals.
- An issue causing incorrect sign and value display for BMS charge current in Storage -> Details has been fixed.
- Reports now display accurate data when Electric Vehicle Charging Stations (EVCS) are in use.
- Timezone additions and corrections in Location Settings are functioning correctly.
- The trickle charging issue has been resolved.
- Oscillations no longer occur when the system is operating with Load Management active, an empty BESS and the system is in one of the following operation modes:
- Peak-Shaving
- Multi-Use
1.12.0
New Features
Microgrid Controller
The EMS now supports the capability to operate a Genset in parallel with a BESS and Loads during offgrid operation. To enable this, the Genset device must be configured within the EMS.
When the BESS State of Charge (SoC) falls below a lower threshold (e.g. 20 %), the EMS will start the Genset to supply power to the load and to charge the BESS. The Genset will be stopped again when the SoC exceeds an upper threshold (e.g. 90%). The SoC band above the upper threshold is performed exclusively when balancing is required for the BMS.
Energy2market Integration
The EMS is able to support both ancillary services, including Frequency Containment Reserve (FCR), Automatic Frequency Restoration Reserve (aFRR), as well as Arbitrage Trading. This capability is facilitated by the integration with Energy2market, which is now supported by the EMS. To utilize these services, users must operate the system in External Control mode and install an e2m-KS control box on-site. Additionally, the Energy2market Modbus register set must be selected under IT-Network → Local Interfaces. The BESS must be marketed via Energy2market.
Privacy Policy
The EMS Privacy Policy is now accessible to logged-in users via the Help menu.
It is also accessible from the Login screen to unauthenticated users.
Changes
Peripheral Devices:
- The Temperature and Humidity Sensor is now visible within the Peripherals list on the Storage → Details page.
- The Fan section on the same page now includes the fan speed, where applicable. This functionality is exclusive to fans of the manufacturer “Weiguang”.
Grid Connection Settings: An informational tooltip has been added to the Maximum grid power withdrawal for EVCS field for clarity on its purpose.
Notifications: The "Cloud connection lost" notification will be issued if the edge-Cloud communication is interrupted for a period exceeding 15 minutes.
Bug fixes
The following issues have been addressed:
- The problem of inverter errors being displayed as unknown errors has been resolved.
- The discrepancy between the BESS/Overall System Status and the status of individual devices has been corrected.
- The issue concerning the sometimes unsuccessful restoration of the External API has been rectified.
- The problem of excessive fan notifications has been resolved.
- The display of invalid temperature readings for the Envicool AC 09-50 has been fixed.
1.11.3
Changes
- Updates to System Overall State displayed in the Portal:
- now, when a BESS or device's worst state is “warning”, the System Overall Status in the Portal will also be “warning”, instead of being “error”.
- a system will now be considered “offline” if the edge device loses communication with the Cloud for 15 minutes or more.
Bug fixes
- The issue with the locations filtering not properly working has been fixed.
1.11.0
New Features
Remote Meters
This feature facilitates the integration of remote grid meters into a main site, enabling the real-time utilization of remote photovoltaic (PV) production/feed-in at the main site to offset local grid consumption. This functionality is exclusively available for main sites operating in Self-Consumption mode. Any surplus remote production will be directed towards charging batteries as required.
Key functionalities
- Ability to mark a grid meter, installed at the remote site, as being “remote-capable”, meaning it can be used at the main site for integration:
- Ability to add into the main site, one or more remote-capable grid meters as PV meters, to be used in the main site’s control loop:
- Ability to see the remote meter in the Dashboard, under the PV tile:
- Ability to draw power from the grid while in self-consumption, a value equal to the one produced at the remote site(s) (limited by the local Mains Connection Point).
Notes:
- This feature can not be set up using the Local UI, only Cloud UI or Mobile App.
- If the remote grid meter detects consumption (e.g. due to current transformers being installed in the false direction), the remote reading defaults to 0 to avoid calculation influence.
- The usage of remote meters is only possible within the same top-level permission group.
Peripherals Status in UI
With this feature, the users have now the possibility to see under Storage > Details > Peripherals, a list of all peripheral devices (fans, air-conditioning devices, fire alarm panels) added into the EMS, alongside their statuses and provided values. The feature is available in Local UI, Cloud UI and Mobile App.
Changes
- Updates to BMS State and IBU State:
- For Pylontech BMS errors read from the device registers, the BMS state and notification type is now "warning" (previously "error").
- This BMS warning state escalates to the IBU state. The IBU state reflects the worst of Inverter and BMS states. When IBU is in a "warning" state, it remains operational (previously was excluded from operations).
Bug fixes
The following issues have been fixed:
- Power distribution to the individual IBUs not working correctly with asymmetric inverter battery configurations.
- Cloud UI slowness when accessing Storage > Details page.
1.10.0
New Features
Genset integration
The following devices can now be added in the EMS:
- Pramac Genset Control Unit DSE 7410 MKIIi
- Pramac Genset Control Unit DSE 8610 MKIIi
The devices’ statuses are shown as follows:
- when a fault is detected, status will be “red”
- when in normal operation mode, status will be “green”
Notifications are sent if the device loses connection, triggers an alarm, or reconnects.
The current EMS version also includes commands that will allow future controllers to turn the devices on or off.
ABL EVCS integration
The ABL Model eM4 (22kW) EVCS can now be integrated into the EMS.
Changes
- For the Pylontech M5, the SoC range has been modified. The minimum State of Charge (SoC) is now 5%, which means that 0% usable SoC corresponds to a nominal SoC of 5%..
- The Pylontech BMS will now display a "warning" state instead of an "error" state when errors are present in its registers. Furthermore, an IBU in a "warning" state will continue to be utilized for operations..
- The ZYC BMS has undergone the following modifications:
- The BMS now reads and saves the BMS Serial Number, Number of Modules per String, Number of Strings in Parallel, and Cycle Count.
- The minimum usable State of Charge (SoC) has been set to 1%.
- The DC Input Voltage is now read, stored, and displayed for the PBI. You can find this information in the "DC INPUT VOLTAGE" column under Storage → Details → Inverter.
- Pramac inverters model names have been corrected, now showing as "PBI 50K", "PBI 88K", "PBI 90K"
- When a PSEC goes offline, a notification of type error is sent to inform the user.
- Device-specific settings are now visible in both view and edit modes for a device.
Bug fixes
The following issues have been fixed:
- The issue where not all BMS values are refreshed automatically under Storage → Details.
- The issue regarding the custom DNS not being saved correctly under System Settings → IT Network → Settings external Network.
- The issue regarding the power distribution not working correctly with asymmetric inverter battery configurations.
1.9.3
Bug fixes
- Slowly loading dashboard has been fixed
- Air-conditioning MC125 fixes
- Fan and Humidity and Temperature Sensor notifications have been adjusted
- Incorrect status for BESS and IBUs has been fixed
- PV-limiting (with SMA DataManager M) fixes
- The issue that during BMS balancing the Mains Grid Connection power is exceeded has been resolved
- The issue that on some systems having peripherals installed, the edge CPU was staying higher than 50% has also been resolved
1.9.0
New Features
Introduction of Battery Energy Storage System (BESS) Structure
The Storage Details section in both the Cloud and Local User Interfaces (UI) has been updated. The updated view now presents Individual Battery Units (IBUs) grouped under the Battery Energy Storage System (BESS). This enhancement will be automatically implemented for Production systems post-release. The initial BESS model will be a Generic model, which users can modify as needed.
The updated view allows users to:
- Create new BESS and IBUs.
- Edit existing BESS and IBUs.
- Delete BESS and IBUs.
- View IBU details in an improved user interface, under the Status tab:
- Perform standard IBU maintenance tasks: manual charging/discharging, scheduled or manual balancing, under the Maintenance tab:
“Datalogger” as a dedicated device type
Previously, dataloggers were created within the EMS as energy meters of type “PV”. Now, with the introduction of the Datalogger device type in the Device Manager, these devices can be created as “Dataloggers”. Support for the same three pre-existing manufacturers (SMA, Solar-Log, and SunGrow) remains.
In the Production environment, all existing devices will be automatically transitioned to Datalogger devices upon migration. Datalogger devices require the configuration of a Nominal Power parameter (representing the PV plant's nominal power [kWp]) during their creation within the Device-specific settings. For devices already in place, this parameter will be automatically assigned a value of "0" during the migration process. If a different value is required, the device must be deleted and then recreated.
Limit PV grid feed-in
The system uses the Datalogger to control PV power flow to the grid, either completely blocking it or limiting export to a user-defined maximum.
Go to System Settings → Grid Connection Point and turn ON “Limit PV grid feed-in”, specifying a “Maximum PV grid feed-in” value. A value of "0" means no feed-in, while a higher value allows feed-in up to that limit. To enable PV grid feed-in limiting, a Datalogger must exist in the EMS, and the nominal power of the PV plant must be known to the EMS.
Note: If a system had previously a datalogger device created as an energy meter and during the new version release the device was transitioned from energy meter to datalogger having the nominal power defaulted to “0”, then the device needs to be deleted and recreated, specifying the nominal power value for the PV plant.
NB: The PV limiting feature can only work with a Solar-Log device if a power management license has been purchased and activated. For SMA and SunGrow dataloggers licenses are not required. For SMA, it might require to activate control via Modbus - please check for your device model before enabling the feature.
When the PV limiting feature is enabled, and the feed-in value is actually limited (completely or partially, the Dashboard will reflect this, see below images for reference:
- completely limited:
- partially limited:
Reports enhanced for EVCS and Storage
The Reports for EVCS and Storage have been extended for the Month, Year and Overall time horizons.
Support for i-charging blueberry EVCS
The following models are now supported in the EMS:
- blueberry 50 kW
- blueberry FUSION 50 - 150 kW
- blueberry PLUS 50 - 900 kW
- blueberry CLUSTER 50 - 900 kW
Support for additional Wallbox Supernova EVCS models
The following models are now supported in the EMS:
- Supernova 60 (60 kW / 2x CCS2)
- Supernova 75 (75 kW / 2x CCS2)
- Supernova 120 (120 kW / 2x CCS2)
- Supernova 150 (150 kW / 2x CCS2)
- Supernova 220 (220 kW/ 2x CCS2)
Support for “ZYC” BMS
The “ZYC SIMPO Pro” is now supported in the EMS.
Changes
The following changes have been made in the latest version:
- Account verification email: The content has been updated and is now also available in English.
- Datalogger Support for SMA PV Inverter Night Saving Mode: Addressed an issue where the datalogger reported incorrect PV production values during SMA PV inverter night saving mode. The system now correctly reports a value of 0 (zero) in these instances, and reports will be adjusted to reflect this accurately.
- EnerCharge EVCS energy reports: in cases when a charging station is removed or replaced the historical data is no longer lost.
- Peripherals - Fan: Updated default fan settings such that fans initiate operation at 50 degrees Celsius. For Weiguang fans, the maximum speed is now activated when the indoor temperature exceeds 75 degrees Celsius.
- Network Time Protocol (NTP): a list of fallback NTP servers for the edge has been implemented. Users retain the ability to configure preferred NTP servers via the UI; however, in the event of failure, the following servers will be utilized as fallback solutions: pool.ntp.org, europe.pool.ntp.org, cn.pool.ntp.org, us.pool.ntp.org.
- Reports: Datapoints within the View selection of Reports are now sorted alphabetically.
- Balancing: Manual balancing is now initiated only when requested by the BMS (BMS balancing requested = true).
- Notifications: Introduced a notification system to inform users when Inverters and BMS return to normal operation following a fault state.
- Gatekeeper: will be enabled by default.
Bug Fixes
The following issues have been addressed:
- Resolved an issue causing Local UI to display some notifications incorrectly.
- Corrected an issue where Inverters ramped up Power if Demand exceeded Mains Grid Connection Power.
- Resolved an issue related to using an incorrect power register for Solar-Log.
- Fixed an issue where latitude and longitude were not updated when editing the system location.
- Addressed an issue causing Reports Overall to display years starting with 1970.
- Rectified an issue where Manual Dis-/Charging did not account for Power Demand exceeding Mains Connections Power.
- Resolved an issue where only the first 10 system notifications were available on the local edge.
- Corrected an issue where System Status did not accurately escalate from children’s worst status.
1.7.0
New features
Peripheral devices integration
The following peripheral devices have been integrated into the EMS:
- Fans:
- Weiguang (Modbus RTU)
- Generic radial fan (DIO)
- Air conditioning (AC):
- Envicool MC06-50 series
- Envicool MC90
- Fire Alarm Control Panel (FACP):
- Kentec SIGMA XT f
The devices can be added within the device manager in both Cloud and Local UI.
FANS
Once created, the fans are automatically controlled by the EMS based on the following temperatures:
- Indoor temperature: This can be taken from the inverters' reported cabinet temperature or a temperature and humidity sensor. This is mandatory, with the default set to the inverters' heat-sink temperature.
- Outdoor temperature: If available, it is provided by an air-conditioning system with an outdoor temperature sensor. This is optional; if not provided, the fan will be controlled only by the indoor temperature.
Note: the reference temperatures must be selected upon device creation (see below screenshot)
Create fan device
Control logic:
- The fan will turn on if the outdoor temperature exceeds 30°C (if outdoor temperature is available) or the indoor temperature reaches 70°C. Once started, it will run for 5 minutes.
- The fan will stop when the reference temperature drops 3°C below the threshold and the 5-minute running time has passed.
Notifications: Alerts are sent when the fan status changes or if the fan can't be controlled due to unavailable reference temperature data.
Please be aware that if a fan has been created and is linked to an Air-Conditioning and/or Temperature and Humidity sensor, the referenced devices cannot be deleted. The fan must be deleted first.
AC
The AC devices use default settings for operation, which cannot be changed in the EMS. The EMS controls the ACs based on these settings.
Alerts are sent when the AC device status changes, including error statuses and device alarms.
FACP
Notifications are sent via UI and mail when the FACP status changes, such as when it enters a fault state or a fire alarm is triggered.
Changes
Introduction of user-friendly notification when reports are not available
Previously, when the report service was unavailable, a technical error message was displayed in the UI. This has been replaced with a user-friendly message informing users that reports are currently unavailable.
Portal pagination extended
The pagination options in the Portal have been extended, now including the options to show 50 and 100 systems in one list.
Portal pagination options
System Settings Enhancements
Under System Settings → Controller → Information, the status of the connection between Edge and Cloud as well as the timestamp when the last connection occurred is now shown, when the status is Disconnected.
System Settings → Controller → Information section
Mobile View Improvements
Several changes have been made to enhance the experience on mobile devices:
- Permissions Group Page: The Edit button is now properly aligned.
- Portal Page (Notifications Section): Display issues have been corrected, ensuring proper information visibility.
- Notifications Modal: Improved layout to better fit mobile screens.
- Enhanced Mobile Usability: The following pages have been adjusted for better mobile compatibility:
- Users
- Permissions Groups
- Photovoltaic → Details
- Charging Stations → Details
- Balancing Settings
- System Settings → IT Network
- Maintenance Page
See below how some of the improved pages look like:
Users page on Mobile
Permission Groups page on Mobile
Photovoltaic Details on Mobile
Balancing Settings on Mobile
Device Status & Notifications changes for Temperature and Humidity Transmitter
If there is no communication with the device, the status light indicator will now turn red. A system notification will be sent whenever there is a status change for this device.
Dashboard Layout Update
The ability to rearrange widgets on the Dashboard has been removed, along with the Reset Layout button. The widgets now have a fixed size and position to prevent misalignment issues.
“Smart meter” label change
The “smart meter” label has been changed to “energy meter” across the application.
Version notes
Version number and link to the current version notes is now available under Help > Version Notes. Edge version refers to the version running on the local PSEC, Cloud version to the version of the Cloud UI. Front end version is for development use only, helpful to be added to issue reports affecting the UI.
Version Notes
Bug fixes
- The issue with the same color being used for multiple charge poles in the Charge Poles → Reports has now been resolved.
- The issue with the IBU name missing from the notification about the balancing issue has been resolved.
- The issue with the energy values for EnerCharge Charge Poles being too small has been fixed as well.
v1.6.0
New Features
Control Point added to Multi-Use operation mode template for Peak-Shaving
The users now have the ability to set different control points for different multi-use operation tasks. To do this:
- Go to Operations Management (in Cloud or Local UI)
- Create a new multi-use task
- Within the task creation template, set the desired control point for this particular multi-use task. The value of the set Control Point is taken into account when the system is doing peak-shaving, as part of the multi-use operation.
After the release, all pre-existing multi-use operation modes in the Production systems will automatically have the Control Point set to the value the system has set under System Settings > Grid Connection Point and all operations should run the same as before.
The Control Point still present in System Settings > Grid Connection Point section is still used as the limit for EVCS Load Management, and it has been relabeled to EVCS LLM limit.
The dashboard widget will only show the Control Point when the system is doing peak-shaving.
Status of the balancing request register displayed under Storage > BMS details for Pylontech BMS
EMS users can see within the EMS UI > Storage > BMS details the status of the BMS in regard to the need of balancing.
Temperature and Humidity sensor integration
Within the EMS, it is now possible to add a temperature and humidity sensor. Its read values (temperature and humidity) will be stored in the EMS local and Cloud database. At this moment in time, these values will not be displayed in the EMS UI. Supported devices:
- Manufacturer: ASAIR, Model: FG6485A
- Manufacturer: MiEnergy, Model: ME-WS-5W
Changes
Improved system notifications for manual charging/discharging operations
- The system notification which expresses that manual charge or discharge has been stopped, contains the name of the corresponding IBU.
- The system notification contains the power value of the charging/discharging operation.
- The system notification correctly shows when manual discharging has been stopped.
- There are proper messages for English and German.
Extended list of supported Alpitronic models
The EMS now can integrate the following EVCS models from the manufacturer Alpitronic:
- HYC 200
- HYC 200 (100 kW / 1x CCS2)
- HYC 200 (100 kW / 1x CCS2 / 1x CHAdeMO)
- HYC 200 (100 kW / 2x CCS2)
- HYC 200 (200 kW / 1x CCS2)
- HYC 200 (200 kW / 1x CCS2 / 1x CHAdeMO)
- HYC 200 (200 kW / 2x CCS2)
- HYC 400
- HYC 400 (100 kW / 1x CCS2)
- HYC 400 (100 kW / 1x CCS2 / 1x CHAdeMO)
- HYC 400 (100 kW / 2x CCS2)
- HYC 400 (100 kW / 2x CCS2 / 1x CHAdeMO)
- HYC 400 (100 kW / 3x CCS2)
- HYC 400 (200 kW / 1x CCS2)
- HYC 400 (200 kW / 1x CCS2 / 1x CHAdeMO)
- HYC 400 (200 kW / 2x CCS2)
- HYC 400 (200 kW / 2x CCS2 / 1x CHAdeMO)
- HYC 400 (200 kW / 3x CCS2)
- HYC 400 (300 kW / 1x CCS2)
- HYC 400 (300 kW / 1x CCS2 / 1x CHAdeMO)
- HYC 400 (300 kW / 2x CCS2)
- HYC 400 (300 kW / 2x CCS2 / 1x CHAdeMO)
- HYC 400 (300 kW / 3x CCS2)
- HYC 400 (400 kW / 1x CCS2)
- HYC 400 (400 kW / 1x CCS2 / 1x CHAdeMO)
- HYC 400 (400 kW / 2x CCS2)
- HYC 400 (400 kW / 2x CCS2 / 1x CHAdeMO)
- HYC 400 (400 kW / 3x CCS2)
Bug fixes
- BMS status now remains correct after deleting the IBU the BMS was part of.
- The issue with the balancing not working has been resolved.
- The issue with the BMS details showing online although the BMS was in error state has been fixed as well.
v1.5.0
New Features
Peak shaving control point can now be configured within the peak shaving operation mode template
Users can now define different control points for each Peak Shaving operation mode. To do this:
- Navigate to Operations Management.
- Create a new task of type Peak Shaving.
- Specify the desired control point (e.g. 30 kW) in the designated input field
- Save the task
Important Notes:
- Pre-existing modes: All existing Peak Shaving operation modes will default to the control point defined under System Settings → Grid Connection Point.
- EVCS Load Management Limit: The control point under System Settings → Grid Connection Point remains the upper limit for EVCS Load Management.
- Multi-Use operation mode: The integration of control points into the Peak Shaving template is not yet available for the Multi-Use operation mode. In this mode, the global control point still applies as both the EVCS Load Management limit and the Peak Shaving control point.
This update gives you greater flexibility to tailor Peak Shaving to your specific operational needs
Mobile Accessibility for Operations Management
The Operations Management page is now fully functional on mobile devices.
Users can now seamlessly access the EMS, view details, and make changes in Operations Management directly from their mobile phones.
This enhancement ensures greater flexibility and accessibility for on-the-go operations.
Battery Cycle count added to BMS Details
The BMS Details section now includes the total number of full battery cycles for batteries connected to the respective BMS.
To view this information, navigate to Storage → IBU → BMS, where the battery cycle count is now displayed. This update provides better insights into battery usage and performance.
Pramac Battery Inverter 90K Integration
The Pramac Battery Inverter 90K (PBI 90K) is now supported and can be added via the Device Manager for use within the EMS.
This enhancement expands compatibility and functionality within the system.
Pylontech Powercube M5 BMS Integration
The Pylontech Powercube M5 BMS is now supported and can be added via the Device Manager for use within the EMS.
This enhancement expands compatibility and functionality within the system.
Bug fixes
- German Translations: Added to the Email Alerts section under System Settings → System State → Email alerts
- Inverter Error Classification: Multiple inverter errors previously labeled as "Unknown Error" have been corrected in both notifications and the Inverter Error Details section.
v1.4.21
New Features
Ability to receive system notifications via email
EMS users can opt to receive system notifications by email. This can be enabled from System Settings > System State > Email Alerts. Users have the option to choose the type of email alerts they wish to receive (information, warning, or error), specify the email addresses of the intended recipients, and save their selections. For each selected notification type, when the system generates a notification, all designated recipients will receive an email. Please refer to the sample screenshot below for reference:
New Device Integration: SMA Data Manager M
The SMA Data Manager M can now be used within the EMS as a smart meter, specifically for photovoltaic systems. Within the EMS, it functions like any other smart meter for PV. Power and energy readings from the device are being displayed in various areas of the EMS where photovoltaic data is relevant: Dashboard, Reports, Photovoltaic (Overview, Details, Reports).
Notifications for inverter and BMS errors
EMS users will receive notifications for inverter and BMS errors within the UI as well as via email.
Daily energy values displayed next to the legend in the Overview chart
EMS users are now able to see the daily energy values displayed next to the legend in the Reports > Overview chart for the following data points:
- Grid consumption
- Grid feed-in
- Charging
- Discharging
- PV production
- Consumption
- EVCS
The values for Grid feed-in, Grid consumption, PV production, and Consumption will continue to be displayed if the user selects Month, Year, or Overall reports.
Please note that these values are refreshed hourly.
Please refer to the sample screenshot below for reference:
Changes
REST API (Cloud + local): Control endpoint updated
The Control endpoint has been updated so that:
- If a charge request exceeds the maxChargeLimit, the system charges at the maxChargeLimit and counts the request as valid, extending the 5-minute period for further requests.
- If a discharge request exceeds the maxDischargeLimit, the system discharges at the maxDischargeLimit and also counts the request as valid, extending the 5-minute period for further requests.
Allow to enter a TCP port for TCP connected devices over UI
When a TCP connected device is being created or updated in the EMS, the user can now enter a TCP port number under the Interface section in order to be able to add devices which do not operate on the standard port.
See below image for reference:
Enhanced mobile views for pages: Dashboard, Notifications and Devices
The Dashboard page, when used on a mobile device, has been updated to show the energy monitor, similar to the desktop version. See screenshot below:
The Notifications and Devices pages have been also updated to better suit the mobile device screen size. Please see the below screenshots for reference:
Notification types
The Notifications page now displays the type of the notification which are either:
- Error
- Warning or
- Information
Until this change, every notification was of type “Information”.
Carlo Gavazzi smart meter setup - Note
The below note appears when a Carlo Gavazzi smart meter is created. Without setting the proper application within the settings of the device, the functionality of the meter readings cannot be assured.
Reports show only PV values higher or equal to zero
In the Reports section, the charts have been revised to display only PV production values that are zero or greater. Any values that were previously negative will now be represented as zero.
Bug fixes
Alpitronic HYC EVCS - energy data values corrected
The Alpitronic HYC EVCS data has been updated for accuracy, with a correction factor of 10 applied. As a result, the values displayed in the Reports and Charging Stations sections for Alpitronic HYC EVCS will now reflect the correct figures.
Example:
EnerCharge EVCS - energy data values corrected
The way energy data from EnerCharge EVCS is read from the devices has been corrected. As a result, the values displayed in the Reports and Charging Stations sections for EnerCharge EVCS will now reflect the correct figures.
Inverter details: grid frequency shown with decimal places
The display of grid frequency value, under Storage > Inverter details has been updated to have two decimal places. Before this change, the value was displayed without the decimal places.
Autarky set to 100 on negative load
Before this change, when the load value was negative, the autarky was displayed as zero. Now, when the load is negative, autarky is 100%, this being visible on the dashboard.
v1.3.9
New Features
Local Modbus TCP interface
The EMS offers the capability to interact with the PSEC via a new local Modbus interface. This feature allows reading and writing certain registers. For details, please refer to the technical documentation.
In order to offer an enhanced user experience when interacting with the EMS for setting up local interfaces, the previously named Local API tab under System Settings > IT Network is now called Local Interfaces and it presents information and options on the preexisting Local REST API as well as the new local Modbus interface. The information and the controls for the REST API have not changed. A new sub-section was added for information and controls on the Modbus interface. In order to use this interface for reading registers, the Read access toggle needs to be enabled. In order to use this interface for writing registers, the Write access toggle needs to be enabled and current operation mode must be External Control.
The page now looks like in the screenshot below:

New UI for Inverter and BMS including error states
In order to enhance the user experience and to provide the place where to display Inverter and BMS errors, under Storage > Details there is an updated user interface that displays together (under the Status page) the information about the Inverter and the BMS as well as the devices states. See a sample screenshot below:

The BMS, Inverter and Settings tabs have been removed. The Maintenance tab remains as before.

In case of errors, near the status of the Inverter or BMS, there is a Details button displayed.

When clicked, a pop-up window is displayed, listing the current errors present in the Inverter or the BMS. See sample screenshots below:

Introduction of energy consumption values in the dashboard and report charts
The EMS dashboard now has a new widget that displays the energy consumption of the day (up until now). See sample below:

Also, in the Overview reports (under the Reports section of the EMS), in the Month, Year and Overall reports, the Consumption data is displayed. See sample below:

Ability to announce planned maintenance in the UI
The EMS now supports informational messages such as announcing planned maintenance time. When enabled, these messages will be shown on each page of the EMS, in the Portal and Edge Cloud UI as well. See below a sample screenshot:

During downtime, when the users will access the EMS, they will be redirected to a maintenance page informing them about ongoing maintenance work. The maintenance page looks like this:

Changes
Cycle loop optimization
Improved control loop to reduce cycle time from ~5 seconds to 2-3 seconds (depending on the grid meter communication interface and protocol).
Performance enhancements
The EMS performance and overall stability has been improved.
Bug Fixes
Cloud UI - Edge
The Photovoltaic > Details page now displays the status of the PV meter correctly, being consistent with the status under Devices list.
Local edge
In the Local edge, under User Menu, the My Profile menu item was removed and the missing Language menu item was re-added.