1.18.0

New Features

Dedicated Consumer Metering

The EMS now supports dedicated consumer energy meters for loads such as heat pumps, cooling systems, heating rods, non-integrated EV charging stations, etc. This makes it possible to monitor individual consumers directly in the platform. Installed consumer meters appear directly in the Dashboard's Consumption section. Additionally, a dedicated entry in the left navigation menu provides access to consumer overviews, detailed analytics, and comprehensive reports. To integrate a new consumer meter into EMS, navigate to Device Manager and add a new energy meter with the “Consumer” type assigned.

Consumers integration in Cloud UI

User-Managed Cloud-2-Cloud (C2C) API Access Control and API Keys

Management of Cloud-2-Cloud API read and write permissions has been introduced to the “System Settings -> External Interface -> REST API -> Cloud” section. The External Interfaces layout has been updated to support this workflow and enhance usability, by grouping the settings for Local REST API and Cloud-2-Cloud REST API under a single main section “REST API”.

User-generated, plant-specific API keys are now available to manage C2C REST API access. Administrators have the ability to rotate keys per plant, enhancing security and offering improved operational management for third-party integrations. Please note that the existing API keys issued before v1.18.0 will expire automatically on December 31, 2026. To prevent any unexpected operational downtime, all C2C API users are encouraged to generate a new key using this new functionality and update their systems accordingly before the end of the year. 

Key Generation Process:

Revocation: Existing keys can be deleted to instantly deactivate them, after which a fresh key can be generated.

Notifications: Key expiration notifications will be triggered and sent via email to registered email addresses in the Plant State -> Email Alerts section.

External Interfaces - New C2C API settings

Enhanced Report Export

The default resolution for report exports has been updated from 1 minute to 15 minutes. This update covers all report categories (including Storage, Photovoltaic, Consumers, Charging Stations, and Overview) across every timeframe (daily, monthly, yearly, and total). Additionally, exported files now align CSV delimiters and decimal separators with the active UI language setting, and relevant column headers now feature units. The change is applied to .csv and .xlsx formats. Please note that the .xls format has been replaced with .xlsx.

External Control in Off-Grid Mode

The operation mode “External Control” now supports off-grid operation, allowing third-party microgrid controllers to control the plant during off-grid operation via the PSEC Modbus TCP Interface. The EMS provides the necessary status registers, operation mode control, and active/reactive power setpoint interfaces needed for advanced external supervision.

IT Network Integration for Auxiliary Devices 

EV charging stations, energy meters for PV and consumers and PV data loggers can now be integrated via the external IT network (LAN 2) where rewiring to the internal OT network is not practical. This gives installers more installation flexibility. When creating a new device, the Link field now presents the two options, where LAN 1 (OT) refers to the internal network and LAN 2 (IT) to the external network. 

Due to security reasons an energy meter of type “Grid” cannot be added via the IT network. 

Device creation - "Link" field options

BMS Balancing Notifications & External APIs

The EMS now exposes battery balancing information more clearly by notifying users when balancing is requested by the BMS and by making that state available through the external interfaces. This helps operators and upstream systems to monitor balancing requests and their potential impact on plant operation. Please consult the REST API or Modbus TCP interface documentation for more information.

 Ziehl EFR4002IP new device integration

Added integration support for the Ziehl EFR4002IP as a grid-only meter.

Changes

Bug Fixes

1.17.9

Bug Fixes

1.17.6

Changes

1.17.5

Changes

Bug Fixes

1.17.4

Changes

1.17.3

Changes

1.17.2

Changes

Bug Fixes

1.17.1

Bug Fixes

1.17.0

New Features

Parallel Generator (Genset) Control 

Added support for managing and running multiple generators (Gensets) simultaneously in parallel. Multiple devices may be configured in the Device Manager and:

Generac Power Zone Controller Integration

Integrated Generac Power Zone PRO Sync controllers to integrate gas generators in off-grid setups. 

Hardy Barth EV Chargers integration 

Expanded system compatibility to support Hardy Barth electric vehicle chargers (V1 & V2), enabling both monitoring and full load management functionality. The following EVCS models can be added and used in the EMS:

NB: These devices use the REST API protocol. Select “REST API” when adding them in Device Manager.

UPDC Integration

Added support for UPDC load-shedding units with PBI inverters to fulfill grid stability requirements in the Italian transmission system (Terna). The remote-controlled device installed at substations or large customers automatically disconnects predefined electrical loads when Terna detects critical grid conditions (like frequency drops or system emergencies), helping stabilize the power system and prevent blackouts. 

Centralized Reactive Power Control via PSEC

Smart Power Plant Controllers / EZA-Regler can now send plant-wide reactive power targets directly to the PSEC instead of having to communicate with each battery inverter individually. The PSEC automatically distributes the target across all connected battery inverters to regulate grid voltage and optimize plant performance. Refer to the PSEC Modbus TCP interface documentation for further details.

Centralized Battery Inverter Power Curtailment via PSEC

Smart Power Plant Controllers / EZA-Regler can now send active power curtailment commands directly to the PSEC via its Modbus TCP interface. The PSEC automatically applies and balances the power limits across all connected battery inverters, removing the need to manage and curtail each inverter individually. Refer to the PSEC Modbus TCP interface documentation for further details.

Battery Flexibility Metrics via Standard Modbus Interface

Third-party energy management systems, SCADA systems, and Smart Power Plant Controllers / EZA-Regler can now read available battery charge and discharge capacities directly through the standard Pramac Modbus TCP interface. This enables integration partners to monitor real-time battery energy availability for grid import and export without requiring specialized market interfaces. Refer to the PSEC Modbus TCP interface documentation for further details.

Configurable Sensor Relay Types 

Added configurable relay contacts (Normally Open / Normally Closed) for temperature, smoke, and ignition sensors. They can be set for each device in the device specific settings.  Example: 

Changes

Bug Fixes

1.16.6

Bug Fixes

The following issues were addressed:

1.16.5

Bug Fixes

The following issues were addressed:

1.16.4

Bug Fixes

The following issues were addressed:

Please note that these updates only required a targeted deployment of Cloud services, so the Cloud version listed in the Version Notes remains unchanged.

1.16.3

New Features

New device integration: Schneider ION9000 series energy meter

The whitelist of supported energy meters has been expanded to include the Schneider ION9000 series energy meter for grid and PV monitoring purposes. The device can be configured within the Device Manager as either a PV or a grid meter.

Bug Fixes

1.16.0

Highlights

New Features

Multi-BESS Architecture

Operating Multi-BESS installations is now more scalable and user-friendly. With the introduction of the plant as the primary operational object, users benefit from an intuitive experience that provides a unified view and simplified oversight of the entire system from a single location.

What is new

  1. Plants are now the main way to view systems 

A new logical Plant level has been introduced to the platform, positioning it above individual edge controllers. A plant can represent either a standalone installation or a Multi-BESS setup configuration, featuring a single primary controller along with one or more secondary controllers.

2.  New Plants section in the Portal

A new Plants section has been added to the Portal. This is the main entry point for viewing and managing customer systems.

In this new section, users can:

Plants page

3. Edge Controllers section replaces the old edge-centric portal model

The previous edge-focused navigation has been simplified. The Edge Controllers section now supports controller-level tasks while the overall operational view moves to the plant level.

Note: End users should expect more day-to-day work to happen from the plant view, while the Edge Controllers area supports more technical or administrative tasks during new system commissionings. 

Edge Controllers page

4. Plant UI replaced Edge (PSEC) UI

Open the “Plant UI” via the location pin next to the plant name to view system details.

Existing systems in the Production environment will automatically get a corresponding plant upon release. In the plant UI, users can still:

Dashboard Storage bubble

System Settings page

5. Local UI - Differentiation between Primary and Secondary Controllers

While the Local UI for a primary controller mirrors the cloud-based Plant UI, the Local UI for a secondary controller is restricted exclusively to the Storage and System Settings (Edge Controller Settings) sections.

Primary PSEC Local UI menu

Secondary PSEC Local UI menu

Who is affected

Constraints and Compatibility Notes

New Off-Grid Operation Modes

  1. Battery-only Mode: This lets the system run entirely on battery power without needing to start the generator, providing more operational flexibility.
  2. Full Mode: Optimizes off-grid performance by enabling the generator and battery to work in tandem, ensuring stable power delivery for BESS operations.

Smart Self-Consumption - Additional PV optimization 

The PV optimization of the Smart Self-Consumption operation mode now includes an additional setting that allows users to enable zero feed-in during negative electricity prices. When activated, PV grid feed-in is prevented during negative price periods, helping to avoid financial losses caused by negative feed-in prices or penalty charges. 

Smart Self-Consumption task template

Modbus TCP interface adds usable SoC register

The PSEC Modbus TCP interface now includes a new register for usable SoC (Address 1080), enabling users to retrieve the same usable SoC value displayed on the UI dashboard. To improve clarity, existing registers were also renamed: register 1004 is now soc_nominal and register 1078 is soc_nominal_remaining_wh

Cloud-2-Cloud API energy endpoints extended with optional SoC parameter

Users can now gain deeper insights into system health by accessing battery SoC data alongside historical energy values through the new optional include_soc parameter. Consult the API documentation for more information.

Invertible energy meters

Saves time and reduces maintenance costs by allowing users to software-invert current flow direction directly from settings, eliminating the need for physical on-site re-installation.

Energy meter device-specific settings

Changes

The following changes are introduced:

Bug fixes

The following issues have been resolved:

1.15.6

Bug fixes

1.15.5

Bug fixes

1.15.4

Bug fixes

1.15.3

Changes

Bug fixes

1.15.1

Changes

Bug fixes

1.15.0

New Features

Integration of the new BSO MAX 125/261 product

Added support for the new BSO MAX 125/261 system, including the Inpower INPPCS-125K inverter and Pylontech M7 BMS. The integration enables configuration, monitoring, and fault management of the system within the EMS, providing the same functionality as existing supported inverter and BMS devices.

Enhanced Smart Self Consumption to avoid PV feed-in during negative price windows

The Smart Self Consumption operation mode is now able to prevent the feeding of solar energy into the grid when spot market prices turn negative. Instead of exporting surplus PV at unfavorable rates, the system intelligently reserves battery capacity to absorb that energy for later self-consumption.

Two new settings give users now full control over the SSC functionalities:

Both are enabled by default and can be adjusted to match users’ preferences.

Fire Suppression System (FSS v2)

Added an enhanced Fire Suppression System integration for BESS units. The system continuously monitors gas, temperature, and smoke sensors to detect early signs of malfunction and prevent thermal runaway. Based on sensor readings, it automatically triggers escalating safety actions — including HVAC force cooling, BESS Safety Stop, and HVAC shutdown. Users can create, edit, and delete an FSS configuration per BESS via the three-dots menu in the Storage Details page, assigning available sensor devices (gas, temperature, smoke) and aerosol suppression systems. FSS status is displayed in a consolidated tile under BESS Peripherals with color-coded sensor states. Supports multiple sensor vendors and models (Kentec, Pramac). The pre-existing "Fire Suppression System" device type in Device Manager has been renamed to "Fire Control Panel" for clarity.

To illustrate the FSS user interface during normal state, please refer to the images below.

Alarm state:

New endpoints in the Cloud-to-Cloud REST API

C2C REST API: Energy values endpoint

Added a new Cloud-to-Cloud REST API endpoint (/api/v1/edge/{edge_id}/energy_values) that allows external partners to retrieve historical and near-real-time energy data for a given system. The endpoint returns values for PV production, load consumption, grid consumption, grid feed-in, BESS charging, and BESS discharging at configurable resolutions (5 min, 15 min, 1 hour, or 1 day), with optional totals. The request is authenticated via API key and includes input validation and a 30-day maximum time horizon. 

C2C REST API: Schedule endpoint for setpoint plans

Added a new Cloud-to-Cloud REST API endpoint (/api/v1/edge/{edgeId}/schedule) that accepts a 24-hour plan of control setpoints in 15-minute intervals (96 entries). This schedule serves as an automatic fallback — if no real-time command is received via the existing /control endpoint within the 5-minute timeout, the system uses the provided schedule to charge (positive values) or discharge (negative values) the BESS. This ensures operational continuity and resilience against connectivity issues. The endpoint includes input validation, handles overlapping setpoints by using the latest, and requires API key authentication.  

Please consult the API documentation for more information.

§14a EnWG grid operator dimming support

Added compliance with §14a EnWG by supporting grid operator curtailment ("dimming") signals. A new device type — Grid operator control box — can be added in the EMS, which receives the DSO signal via a potential-free dry contact (GPIO). When the dimming signal is active, BESS grid charging power is automatically limited to 4.2 kW. Normal operation resumes once the signal is withdrawn; grid feed-in remains unaffected. 

Added support for Wallbox SUPERNOVA 240 charger

The Wallbox SUPERNOVA 240 (240 kW / 2× CCS2) has been added to the list of supported Wallbox chargers in the device manager. Users can now select and configure this charger directly through the EMS interface.

Added support for Mennekes AMTRON 4Business 700 charger series

The device manager now includes the "AMTRON 4Business 700" series (11 kW and 22 kW, Typ 2) as selectable chargers, ensuring all officially supported Mennekes EV charging stations are available for configuration in the EMS.

Changes

1. Dashboard, Sidebar Menu and new widgets: 

2. Handling energy value drops on Janitza energy meters: Resolved an issue where Janitza meters occasionally reported decreasing energy values (production/consumption), causing incorrect spikes in reports. The system now detects and ignores short-duration glitches in energy readings, ensuring consumption and production reports remain accurate and free of anomalous spikes.

3. Enhanced charging control to maintain reserved SoC: Added intelligent charging power control to ensure the battery's reserved State of Charge (SoC) is maintained. When the actual SoC drops below the reserved level, the system now automatically initiates charging at the appropriate power level — while respecting grid connection point limits and control point constraints. This ensures the reserved energy buffer is always available for backup scenarios without violating physical grid limitations.

4. PV plant configuration improvements & PV forecast clipping: Redesigned the PV plant configuration interface with improved usability, including intuitive azimuth and tilt angle controls with slider and direct input. Introduced PV forecast clipping, which caps the PV forecast value at the inverter's Max AC Power — ensuring forecasts never exceed what the inverter can actually deliver. Also added sun tracker support (fixed orientation / tracking mode) for more accurate forecast parameters. Please refer to the image below:

5. MAC address field removed: Adding a new network device does no longer require the input of its MAC address. The existing MAC address field has been removed.

6. Output PIN configuration for GPIO fan device: Users can now select and configure the output PIN for GPIO fan devices directly from the device specific-settings.

7. Full battery discharge prevention in off-grid systems without a Genset: the EMS now automatically shuts down inverters when battery SoC drops below the minimum safe threshold to prevent full discharge and BMS errors. 

Bug Fixes

The following issues have been resolved:

1.14.9

Changes

1.14.8

Changes

1.14.7

Changes

1.14.6

Changes

1.14.5

Changes

1.14.4

Changes

1.14.3

Changes

1.14.1

Changes

Bug fixes

1.14.0

New Features

Implementation of a dynamic control point for peak shaving operation 

The peak shaving operation mode has been enhanced to support dynamic configuration of the control point via the Modbus TCP interface. For detailed technical specifications on integrating this functionality, please refer to the Pramac EMS Modbus TCP interface documentation.

Advanced Microgrid Control

Pramac C&I PRO BESS systems now include advanced microgrid control. This enables users to monitor and configure Backup and full off-grid operation, including genset integration and PV curtailment management. New user interface components have been added to support monitoring and configuration of these modes.

Highlights

Changes

  1. Modbus TCP Interface extension: External devices can now access additional data points via the Modbus TCP interface, including BESS state of charge (Wh), maximum charge and discharge power, grid import and export energy, as well as BESS and PV energy flows. For further details, refer to the Modbus TCP interface documentation.
  2. Operational IBU data display: Calculations for BESS capacity and nominal SoC now consider only operational IBUs.
  3. Pagination in Portal: Users can now view all systems within the Portal.
  4. Local UI Update: The Reports section has been removed from the Local UI to streamline the interface and focus on core functionality.
  5. Cloud Application Performance Improvements: Performance of cloud microservices has been improved

Bug Fixes

The following issues have been resolved:

1.13.0

New Features

Smart Self-Consumption

A new operation mode (“Smart Self-Consumption”) has been added to the EMS. This feature is designed to minimize electricity costs by optimizing the charging of the BESS. It uses load forecasts, PV forecasts and day ahead spot-market prices to determine the most cost-effective intervals when to charge the BESS.

Forecasts

The forecasted values are visualized in the following sections:

New operation mode

A new operation mode (“Smart Self-Consumption”) is now available in the Operations Management.

Important Note: in order to use this feature please contact us.

Genset displayed in Energy Monitor

The EMS now displays the Genset in the Dashboard, when such a device has been added in the EMS.

Balancing power input field

Users can now specify the balancing power. It defaults to the inverter's nominal power. The actual balancing power is limited by both the BMS and inverter, applying to manual and scheduled balancing.

Changes

  1. Improved edge application performance and maintainability.
  2. Added BESS models: "BSO MAX 90/188" and "BSO MAX PRO 90/188."
  3. The active IBU count under Storage > Details now includes IBUs with a “warning” status.
  4. Adjustments have been made to mitigate excessive notifications caused by volatile communication issues between the PSEC and devices.

Bug fixes

The following issues have been addressed and resolved in this release:

1.12.0

New Features

Microgrid Controller

The EMS now supports the capability to operate a Genset in parallel with a BESS  and Loads during offgrid operation. To enable this, the Genset device must be configured within the EMS.

When the BESS State of Charge (SoC) falls below a lower threshold (e.g. 20 %), the EMS will start the Genset to supply power to the load and to charge the BESS. The Genset will be stopped again when the SoC exceeds an upper threshold (e.g. 90%). The SoC band above the upper threshold is performed exclusively when balancing is required for the BMS.

Energy2market Integration

The EMS is able to support both ancillary services, including Frequency Containment Reserve (FCR), Automatic Frequency Restoration Reserve (aFRR), as well as Arbitrage Trading. This capability is facilitated by the integration with Energy2market, which is now supported by the EMS. To utilize these services, users must operate the system in External Control mode and install an e2m-KS control box on-site. Additionally, the Energy2market Modbus register set must be selected under IT-Network → Local Interfaces. The BESS must be marketed via Energy2market.

Privacy Policy

The EMS Privacy Policy is now accessible to logged-in users via the Help menu.

It is also accessible from the Login screen to unauthenticated users.

Changes

Peripheral Devices:

Grid Connection Settings: An informational tooltip has been added to the Maximum grid power withdrawal for EVCS field for clarity on its purpose.

Notifications: The "Cloud connection lost" notification will be issued if the edge-Cloud communication is interrupted for a period exceeding 15 minutes.

Bug fixes

The following issues have been addressed:

1.11.3

Changes

Bug fixes

1.11.0

New Features

Remote Meters

This feature facilitates the integration of remote grid meters into a main site, enabling the real-time utilization of remote photovoltaic (PV) production/feed-in at the main site to offset local grid consumption. This functionality is exclusively available for main sites operating in Self-Consumption mode. Any surplus remote production will be directed towards charging batteries as required.

Key functionalities

Notes: 

Peripherals Status in UI

With this feature, the users have now the possibility to see under Storage > Details > Peripherals, a list of all peripheral devices (fans, air-conditioning devices, fire alarm panels) added into the EMS, alongside their statuses and provided values. The feature is available in Local UI, Cloud UI and Mobile App. 

Changes

Bug fixes

The following issues have been fixed:

1.10.0

New Features

Genset integration

The following devices can now be added in the EMS:

The devices’ statuses are shown as follows: 

Notifications are sent if the device loses connection, triggers an alarm, or reconnects.

The current EMS version also includes commands that will allow future controllers to turn the devices on or off.

ABL EVCS integration

The ABL Model eM4 (22kW) EVCS can now be integrated into the EMS.

Changes

Bug fixes

The following issues have been fixed:

1.9.3

Bug fixes

1.9.0

New Features

Introduction of Battery Energy Storage System (BESS) Structure

The Storage Details section in both the Cloud and Local User Interfaces (UI) has been updated. The updated view now presents Individual Battery Units (IBUs) grouped under the Battery Energy Storage System (BESS). This enhancement will be automatically implemented for Production systems post-release. The initial BESS model will be a Generic model, which users can modify as needed.

The updated view allows users to:

“Datalogger” as a dedicated device type 

Previously, dataloggers were created within the EMS as energy meters of type “PV”. Now, with the introduction of the Datalogger device type in the Device Manager, these devices can be created as “Dataloggers”. Support for the same three pre-existing manufacturers (SMA, Solar-Log, and SunGrow) remains.

In the Production environment, all existing devices will be automatically transitioned to Datalogger devices upon migration. Datalogger devices require the configuration of a Nominal Power parameter (representing the PV plant's nominal power [kWp]) during their creation within the Device-specific settings. For devices already in place, this parameter will be automatically assigned a value of "0" during the migration process. If a different value is required, the device must be deleted and then recreated.

Limit PV grid feed-in

The system uses the Datalogger to control PV power flow to the grid, either completely blocking it or limiting export to a user-defined maximum.

Go to System Settings → Grid Connection Point and turn ON “Limit PV grid feed-in”, specifying a “Maximum PV grid feed-in” value. A value of "0" means no feed-in, while a higher value allows feed-in up to that limit. To enable PV grid feed-in limiting, a Datalogger must exist in the EMS, and the nominal power of the PV plant must be known to the EMS.

Note: If a system had previously a datalogger device created as an energy meter and during the new version release the device was transitioned from energy meter to datalogger having the nominal power defaulted to “0”, then the device needs to be deleted and recreated, specifying the nominal power value for the PV plant.

NB: The PV limiting feature can only work with a Solar-Log device if a power management license has been purchased and activated. For SMA and SunGrow dataloggers licenses are not required. For SMA, it might require to activate control via Modbus - please check for your device model before enabling the feature.

When the PV limiting feature is enabled, and the feed-in value is actually limited (completely or partially, the Dashboard will reflect this, see below images for reference:

Reports enhanced for EVCS and Storage

The Reports for EVCS and Storage have been extended for the Month, Year and Overall time horizons.

Support for i-charging blueberry EVCS

The following models are now supported in the EMS:

Support for additional Wallbox Supernova EVCS models

The following models are now supported in the EMS:

Support for “ZYC” BMS

The “ZYC SIMPO Pro” is now supported in the EMS.

Changes

The following changes have been made in the latest version:

  1. Account verification email: The content has been updated and is now also available in English.
  2. Datalogger Support for SMA PV Inverter Night Saving Mode: Addressed an issue where the datalogger reported incorrect PV production values during SMA PV inverter night saving mode. The system now correctly reports a value of 0 (zero) in these instances, and reports will be adjusted to reflect this accurately.
  3. EnerCharge EVCS energy reports: in cases when a charging station is removed or replaced the historical data is no longer lost.
  4. Peripherals - Fan: Updated default fan settings such that fans initiate operation at 50 degrees Celsius. For Weiguang fans, the maximum speed is now activated when the indoor temperature exceeds 75 degrees Celsius.
  5. Network Time Protocol (NTP): a list of fallback NTP servers for the edge has been implemented. Users retain the ability to configure preferred NTP servers via the UI; however, in the event of failure, the following servers will be utilized as fallback solutions: pool.ntp.org, europe.pool.ntp.org, cn.pool.ntp.org, us.pool.ntp.org.
  6. Reports: Datapoints within the View selection of Reports are now sorted alphabetically.
  7. Balancing: Manual balancing is now initiated only when requested by the BMS (BMS balancing requested = true).
  8. Notifications: Introduced a notification system to inform users when Inverters and BMS return to normal operation following a fault state.
  9. Gatekeeper: will be enabled by default.

Bug Fixes

The following issues have been addressed:

  1. Resolved an issue causing Local UI to display some notifications incorrectly.
  2. Corrected an issue where Inverters ramped up Power if Demand exceeded Mains Grid Connection Power.
  3. Resolved an issue related to using an incorrect power register for Solar-Log.
  4. Fixed an issue where latitude and longitude were not updated when editing the system location.
  5. Addressed an issue causing Reports Overall to display years starting with 1970.
  6. Rectified an issue where Manual Dis-/Charging did not account for Power Demand exceeding Mains Connections Power.
  7. Resolved an issue where only the first 10 system notifications were available on the local edge.
  8. Corrected an issue where System Status did not accurately escalate from children’s worst status.

1.7.0

New features

Peripheral devices integration

The following peripheral devices have been integrated into the EMS:

The devices can be added within the device manager in both Cloud and Local UI.

FANS

Once created, the fans are automatically controlled by the EMS based on the following temperatures:

Note: the reference temperatures must be selected upon device creation (see below screenshot)

Create fan device

Control logic:

Notifications: Alerts are sent when the fan status changes or if the fan can't be controlled due to unavailable reference temperature data.

Please be aware that if a fan has been created and is linked to an Air-Conditioning and/or Temperature and Humidity sensor, the referenced devices cannot be deleted. The fan must be deleted first.

AC

The AC devices use default settings for operation, which cannot be changed in the EMS. The EMS controls the ACs based on these settings.

Alerts are sent when the AC device status changes, including error statuses and device alarms.

FACP

Notifications are sent via UI and mail when the FACP status changes, such as when it enters a fault state or a fire alarm is triggered.

Changes

Introduction of user-friendly notification when reports are not available

Previously, when the report service was unavailable, a technical error message was displayed in the UI. This has been replaced with a user-friendly message informing users that reports are currently unavailable.

Portal pagination extended

The pagination options in the Portal have been extended, now including the options to show 50 and 100 systems in one list.

Portal pagination options

System Settings Enhancements

Under System Settings → Controller → Information, the status of the connection between Edge and Cloud as well as the timestamp when the last connection occurred is now shown, when the status is Disconnected. 

System Settings → Controller → Information section

Mobile View Improvements

Several changes have been made to enhance the experience on mobile devices:

See below how some of the improved pages look like:

Users page on Mobile

Permission Groups page on Mobile

Photovoltaic Details on Mobile

Balancing Settings on Mobile

Device Status & Notifications changes for Temperature and Humidity Transmitter

If there is no communication with the device, the status light indicator will now turn red. A system notification will be sent whenever there is a status change for this device.

Dashboard Layout Update

The ability to rearrange widgets on the Dashboard has been removed, along with the Reset Layout button. The widgets now have a fixed size and position to prevent misalignment issues.

“Smart meter” label change

The “smart meter” label has been changed to “energy meter” across the application. 

Version notes

Version number and link to the current version notes is now available under Help > Version Notes. Edge version refers to the version running on the local PSEC, Cloud version to the version of the Cloud UI. Front end version is for development use only, helpful to be added to issue reports affecting the UI.

Version Notes

Bug fixes

v1.6.0

New Features

Control Point added to Multi-Use operation mode template for Peak-Shaving

The users now have the ability to set different control points for different multi-use operation tasks. To do this:

  1. Go to Operations Management (in Cloud or Local UI)
  2. Create a new multi-use task
  3. Within the task creation template, set the desired control point for this particular multi-use task. The value of the set Control Point is taken into account when the system is doing peak-shaving, as part of the multi-use operation.

After the release, all pre-existing multi-use operation modes in the Production systems will automatically have the Control Point set to the value the system has set under System Settings > Grid Connection Point and all operations should run the same as before.

The Control Point still present in System Settings > Grid Connection Point section is still used as the limit for EVCS Load Management, and it has been relabeled to EVCS LLM limit. 

The dashboard widget will only show the Control Point when the system is doing peak-shaving.

Status of the balancing request register displayed under Storage > BMS details for Pylontech BMS

EMS users can see within the EMS UI > Storage > BMS details the status of the BMS in regard to the need of balancing. 

Temperature and Humidity sensor integration

Within the EMS, it is now possible to add a temperature and humidity sensor. Its read values (temperature and humidity) will be stored in the EMS local and Cloud database. At this moment in time, these values will not be displayed in the EMS UI. Supported devices:

  1. Manufacturer: ASAIR, Model: FG6485A
  2. Manufacturer: MiEnergy, Model: ME-WS-5W

Changes 

Improved system notifications for manual charging/discharging operations

Extended list of supported Alpitronic models

The EMS now can integrate the following EVCS models from the manufacturer Alpitronic:

Bug fixes

v1.5.0

New Features

Peak shaving control point can now be configured within the peak shaving operation mode template

Users can now define different control points for each Peak Shaving operation mode. To do this:

Important Notes:

This update gives you greater flexibility to tailor Peak Shaving to your specific operational needs

Mobile Accessibility for Operations Management

The Operations Management page is now fully functional on mobile devices.

Users can now seamlessly access the EMS, view details, and make changes in Operations Management directly from their mobile phones. 
This enhancement ensures greater flexibility and accessibility for on-the-go operations.

Battery Cycle count added to BMS Details

The BMS Details section now includes the total number of full battery cycles for batteries connected to the respective BMS.

To view this information, navigate to Storage → IBU → BMS, where the battery cycle count is now displayed. This update provides better insights into battery usage and performance.

Pramac Battery Inverter 90K Integration

The Pramac Battery Inverter 90K (PBI 90K) is now supported and can be added via the Device Manager for use within the EMS.

This enhancement expands compatibility and functionality within the system.

Pylontech Powercube M5 BMS Integration

The Pylontech Powercube M5 BMS is now supported and can be added via the Device Manager for use within the EMS.

This enhancement expands compatibility and functionality within the system.

Bug fixes

v1.4.21

New Features

Ability to receive system notifications via email

EMS users can opt to receive system notifications by email. This can be enabled from System Settings > System State > Email Alerts. Users have the option to choose the type of email alerts they wish to receive (information, warning, or error), specify the email addresses of the intended recipients, and save their selections. For each selected notification type, when the system generates a notification, all designated recipients will receive an email. Please refer to the sample screenshot below for reference:

New Device Integration: SMA Data Manager M

The SMA Data Manager M can now be used within the EMS as a smart meter, specifically for photovoltaic systems. Within the EMS, it functions like any other smart meter for PV. Power and energy readings from the device are being displayed in various areas of the EMS where photovoltaic data is relevant: Dashboard, Reports, Photovoltaic (Overview, Details, Reports).
 

Notifications for inverter and BMS errors

EMS users will receive notifications for inverter and BMS errors within the UI as well as via email.

Daily energy values displayed next to the legend in the Overview chart

EMS users are now able to see the daily energy values displayed next to the legend in the Reports > Overview chart for the following data points:

The values for Grid feed-in, Grid consumption, PV production, and Consumption will continue to be displayed if the user selects Month, Year, or Overall reports. 

Please note that these values are refreshed hourly.

Please refer to the sample screenshot below for reference:

Changes 

REST API (Cloud + local): Control endpoint updated

The Control endpoint has been updated so that:

  1. If a charge request exceeds the maxChargeLimit, the system charges at the maxChargeLimit and counts the request as valid, extending the 5-minute period for further requests.
  2. If a discharge request exceeds the maxDischargeLimit, the system discharges at the maxDischargeLimit and also counts the request as valid, extending the 5-minute period for further requests.

Allow to enter a TCP port for TCP connected devices over UI

When a TCP connected device is being created or updated in the EMS, the user can now enter a TCP port number under the Interface section in order to be able to add devices which do not operate on the standard port.

See below image for reference:

Enhanced mobile views for pages: Dashboard, Notifications and Devices 

The Dashboard page, when used on a mobile device, has been updated to show the energy monitor, similar to the desktop version. See screenshot below:

The Notifications and Devices pages have been also updated to better suit the mobile device screen size. Please see the below screenshots for reference:
 

Notification types

The Notifications page now displays the type of the notification which are either:

Until this change, every notification was of type “Information”.

Carlo Gavazzi smart meter setup - Note

The below note appears when a Carlo Gavazzi smart meter is created. Without setting the proper application within the settings of the device, the functionality of the meter readings cannot be assured.

Reports show only PV values higher or equal to zero

In the Reports section, the charts have been revised to display only PV production values that are zero or greater. Any values that were previously negative will now be represented as zero.

Bug fixes

Alpitronic HYC EVCS - energy data values corrected

The Alpitronic HYC EVCS data has been updated for accuracy, with a correction factor of 10 applied. As a result, the values displayed in the Reports and Charging Stations sections for Alpitronic HYC EVCS will now reflect the correct figures.

Example:

EnerCharge EVCS - energy data values corrected

The way energy data from EnerCharge EVCS is read from the devices has been corrected. As a result, the values displayed in the Reports and Charging Stations sections for EnerCharge EVCS will now reflect the correct figures.

Inverter details: grid frequency shown with decimal places

The display of grid frequency value, under Storage > Inverter details  has been updated to have two decimal places. Before this change, the value was displayed without the decimal places.

Autarky set to 100 on negative load

Before this change, when the load value was negative, the autarky was displayed as zero. Now, when the load is negative, autarky is 100%, this being visible on the dashboard.

v1.3.9

New Features

Local Modbus TCP interface

The EMS offers the capability to interact with the PSEC via a new local Modbus interface. This feature allows reading and writing certain registers. For details, please refer to the technical documentation.

In order to offer an enhanced user experience when interacting with the EMS for setting up local interfaces, the previously named Local API tab under System Settings > IT Network is now called Local Interfaces and it presents information and options on the preexisting Local REST API as well as the new local Modbus interface. The information and the controls for the REST API have not changed. A new sub-section was added for information and controls on the Modbus interface. In order to use this interface for reading registers, the Read access toggle needs to be enabled. In order to use this interface for writing registers, the Write access toggle needs to be enabled and current operation mode must be External Control.

The page now looks like in the screenshot below: 

New UI for Inverter and BMS including error states

In order to enhance the user experience and to provide the place where to display Inverter and BMS errors, under Storage > Details there is an updated user interface that displays together (under the Status page) the information about the Inverter and the BMS as well as the devices states. See a sample screenshot below: 

The BMS, Inverter and Settings tabs have been removed. The Maintenance tab remains as before. 

In case of errors, near the status of the Inverter or BMS, there is a Details button displayed. 

When clicked, a pop-up window is displayed, listing the current errors present in the Inverter or the BMS. See sample screenshots below: 

Introduction of energy consumption values in the dashboard and report charts

The EMS dashboard now has a new widget that displays the energy consumption of the day (up until now). See sample below: 

Also, in the Overview reports (under the Reports section of the EMS), in the Month, Year and Overall reports, the Consumption data is displayed. See sample below: 

Ability to announce planned maintenance in the UI

The EMS now supports informational messages such as announcing planned maintenance time. When enabled, these messages will be shown on each page of the EMS, in the Portal and Edge Cloud UI as well. See below a sample screenshot: 

During downtime, when the users will access the EMS, they will be redirected to a maintenance page informing them about ongoing maintenance work. The maintenance page looks like this: 
 

Changes

Cycle loop optimization

Improved control loop to reduce cycle time from ~5 seconds to 2-3 seconds (depending on the grid meter communication interface and protocol). 

Performance enhancements

The EMS performance and overall stability has been improved. 

Bug Fixes

Cloud UI - Edge

The Photovoltaic > Details page now displays the status of the PV meter correctly, being consistent with the status under Devices list.

Local edge

In the Local edge, under User Menu, the My Profile menu item was removed and the missing Language menu item was re-added.